Testing Requirements
Class
EN ISO 1716
EN 50399 (20,5 KW flam source for B2ca, Cca, Dca; 30KW for B1ca)
EN 61034-2
EN 60754-2
EN 60332-1-2
PCS
(MJ/kg)THR1200S
(MJ)Peak HRR
(KW)FIGRA
(W/s)FS
(m)TSP1200S
(m2)Peak SPR
(m2/s)Flaming droplets
/particlesTransmittance
Conductivity and pH
(us/mm)H
Aca
<=2.0
/
/
/
/
/
/
/
/
/
/
B1ca
/
<=10
<=20
<=120
<=1.75
/
/
/
/
/
<425 mm
B2ca
/
<=15
<=30
<=150
<=1.5
/
/
/
/
/
<425 mm
Cca
/
<=30
<=60
<=300
<=2
/
/
/
/
/
<425 mm
Dca
/
<=70
<=400
<=1300
/
/
/
/
/
/
<425 mm
Eca
/
/
/
/
/
/
/
/
/
/
<425 mm
Fca
NPD
s1
<=50
<=0.25
s1a
<=50
<=0.25
>=80%
s1b
<=50
<=0.25
>=60%<80%
s2
<=400
<=1.5
s3
Products for which no performance is declared or which do not comply with the s1 and s2 criteria.
d0
no droplets occur within 1200 s
d1
less than 10 s occur within 1200 s
d2
Products for which no performance is declared or which do not comply with the d0 and d1 criteria.
a1
<2.5; pH>4.3
a2
<10; pH>4.3
a3
Products for which no performance is declared or which do not comply with the a1 and a2 criteria.