Application
The cable is used to exchange information between different automation systems and interconnect L2-BUS components. It is suitable for outdoor use with PE jacket and industry with PUR jacket.
Technical data
Cable weight: 64.0 kg/km
Copper weight: 24.0 kg/km
Minimum bending radius for laying: 120 mm
Temperature Range: -40 °C to +70 °C
Cable structure
Conductor: bare copper; 1 x 2 x 0.64 mm
Insulation: foam-skin-PE
Core colors: red, green
Stranding element: 2 cores + 2 fillers stranded together
Shielding 1: Al-PET foil
Shielding 2: tinned copper braiding
Outer sheath material: PE/PUR
Cable external diameter: 7.8 mm +/- 0.2 mm
Electrical data
Characteristic impedance: 150 Ohm +/- 10%
Conductor resistance: 55.0 Ohm/km
Insulation resistance: 1.00 GOhm x km
Mutual capacitance: 30.0 nF/km
Test voltage: 1.5 KV
Attenuation
9.6 kHz <2.5 dB/km
38.4 kHz <4.0 dB/km
4 MHz <22.0 dB/km
16 MHz <42.0 dB/km
Standard:
Profibus acc. toDIN 19245 T3 and EN50170